High Performance

Full galvanic isolation for safer operation and stronger load adaptability

Suitable to recharge standard and external battery packs for back-up times up to several hours.

High input performance with wide input voltage range, PF=1 and low harmonic distortion

Complete solution with built-in static and manual bypass switch

Rugged design suitable for harsh operating environments

Comprehensive and visualized LCD display, rich information including working status and operating data

 Flexible Design

  • Output voltage is selectable via LCD
    • Batteries total quantity settable, 16 to 20x12V blocks
    • SNMP or RS485+dry contact
    • Charging voltage temperature compensation
  • Parallel function

Specifications

MODELEN6-11EN10-11
INPUT
Voltage (Vac)80~275
Frequency (Hz)50/60± 10% (50/60Hz auto-sensing)
Power Factor≥0.99
THDi<5%
Phase3W (L+N+G/L1+L2+G)
OUTPUT
Capacity (kVA)610
Power Factor0.9
Voltage (Vac)120/208/220/230/240±1% (settable on display panel and output wiring line)
Frequency (Hz)50/60±0.2% (battery mode)
THDvTHD<1% (linear load), THD<5% (nonlinear load)
Transfer Time (ms)0
EfficiencyUp to 95%
Crest Factor3:1
Overload125% for 10mins
Battery
Battery Voltage (Vdc)192 (192~240V settable)
Battery Type16×7Ah12V/External16×9Ah12V/External
Charging Current (A)1A (default); 1~8A settable
OTHER
Communication InterfaceRS232, EPO (SNMP, USB, RS485+dry contact
LCD DisplayAC input & output voltage, frequency, Load level, Battery level, Temperature.
AC mode, Battery mode, Bypass mode, and Fault
AlarmLow battery, abnormal AC input, UPS failure
ProtectionLow battery, overload, short-circuit and over temperature, etc.
Noise (dB4550
Working Temperature (℃)-5~40
Relative Humidity0~95%, No condensation
Dimension (W×D×H) (mm)250×660×720
Weight (Kg)104/68128/88
Scroll to Top